Print Form
™
ECO-i Submittal Data
CHDZ09053
Heat Recovery: 8 tons VRF Outdoor Unit
Job Name:
Location:
Approval:
Date:
Engineer:
Construction:
Unit #:
Drawing #:
Submitted to:
Submitted by:
Reference:
Compressor Warranty: 6 Years
Parts Warranty: 1 Year
Coil Coated to Protect Against Corrosion
Salt Protection also avilable
Capacities
Fan
Cooling: Btu/h
Power Input: KW
Heating: Btu/h
Power Input: KW
95,500
8.12
107,500
7.97
Quantity/Type:
Fan Motor Output (KW):
1 Propeller
0.7
Power Supply
V/PH/Hz.
208-230 / 3 / 60
Cooling Mode Nominal Conditions
Indoor: °F DB/°F WB
Outdoor: °F DB
Minimum circuit Amps (MCA): Amps
Max. Overcurrent Protection (MOCP):
37
50
80/67
95
25
Pipe Length (feet):
Weight (lbs):
657
Level Difference (feet):
0
Refrigerant:
410A
Heating Mode Nominal Conditions
Indoor: °F DB
Outdoor: °F DB/ °F WB
Pipe Length (feet):
70
47/43
25
Coil
Coil Face Area (sq. ft.):
Number of Rows:
22.5
4
Level Difference (feet):
0
Protection Devices
High Pressure Switch:
Overcurrent (CT Method):
Crankcase Heaters (W):
Operating Range
Cooling: °F DB:
Heating: °F DB:
Yes
Yes
25 + 32
14 to 109
-4 to 59
Compressor
External Finish:
Electrostatic Powder Coating
Quantity/Type:
1 Inverter driven rotary & 1 fxed speed scroll
Capacity Control Range:
10-100%
|
Mtd Automobile Parts 357cc User Manual
Omega Flowmeter Fl 1500a User Manual
Oreck Air8 Series User Manual
Radio Shack 23 418 User Manual
Samsung As12cm2x User Manual
Spt Wa 8011s User Manual
Toshiba All In One Printer 203s User Manual
Xerox All In One Printer 2121 User Manual
York 10 Seer 50hz R22 User Manual
York Millennium Nd480 User Manual